Commissioning, 18 english – Lenze ETMD Tmd frequency inverter User Manual

Page 19

Advertising
background image

18

ENGLISH

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

Serial baud rate

0

0 LECOM: 9600 bps
Modbus: 9600,8,N,2

• See C01
• LECOM if C01 = 0...3
• Modbus if C01 = 8...11

1 LECOM: 4800 bps
Modbus: 9600,8,N,1

2 LECOM: 2400 bps
Modbus: 9600,8,E,1

3 LECOM: 1200 bps
Modbus: 9600,8,O,1

Frequency setpoint via
keys

or Modbus

0.0

0.0

{Hz}

240 Only active if C01 is set properly

(C01 = 1, 5, 7, 9, 11)

Start condition
(with mains on)

1

0

Start after LOW-HIGH
change at terminal 28

See also c43 and c70

1

Auto start if terminal 28 = HIGH

2

Flying restart (auto start disabled)

3

Auto start if terminal 28 = HIGH,
with flying restart

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to personnel!
Automatic starting/restarting should only be used on equipment that is inaccessible to
personnel.

Flying restart selection

0

0

Search range: C11...0 Hz

If c42 = 2 or 3, the controller will start the
motor speed search at C11, or at the last
output frequency before the fault, depending
on the setting of c43

1

Search range: last frequency...0 Hz

Motor auto-calibration

0

0

Calibration not done

• If C14 = 4...7, motor calibration must

be performed, but C86...C91 must be
programmed first (see C14)

• If motor calibration is attempted before

programming C86...C91, triggers

fault

1

Calibration enabled

2

Calibration complete

6

Mode selection for c61

0

0

Monitoring only

c60 = 1 allows the keys

to adjust

speed setpoint (c40) while monitoring c61

1

Monitoring and editing

1

Present status/error

status/error message

• Display
• Refer to Section 5 for explanation of status

and error messages

Last error

error message

Last error but one

Last error but two