Commissioning, 13 english – Lenze ETMD Tmd frequency inverter User Manual

Page 14

Advertising
background image

13

ENGLISH

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

Configuration -
Digital input E1

1

1

Activate fixed setpoint 1 (JOG1)

Activate JOG3: Both terminals = HIGH

2

Activate fixed setpoint 2 (JOG2)

3

DC braking (DCB)

see also C36

4

Direction of rotation

LOW = CW rotation
HIGH = CCW rotation

Configuration -
Digital input E2

2

5

Quick stop

Controlled deceleration to standstill, active
LOW; Set decel rate in C13 or c03

6

CW rotation

7

CCW rotation

CW rotation = LOW and CCW rotation =
LOW: Quick stop; Open-circuit protected

Configuration -
Digital input E3

3

8

UP (setpoint ramp-up)

9

DOWN (setpoint ramp-down)

UP = LOW and DOWN = LOW: Quick stop;
Use momentary NC contacts

10 TRIP set

Active LOW, triggers

(motor coasts to

standstill)

NOTE:

NC thermal contact from the motor

can be used to trigger this input

Configuration -
Digital input E4

4

11 TRIP reset

see also c70

12 Accel/decel 2

see c01 and c03

Note

A

fault will occur under the following conditions:

• E1...E4 settings are duplicated (each setting can only be used once)
• One input is set to UP and another is not set to DOWN, or vice-versa

Network address

1

1

247 Each controller on network must have

unique address

C1

Minimum output
frequency

0.0

0.0

{Hz}

240 • Output frequency at 0% analog setpoint

• C10 not active for fixed setpoints or

setpoint selection via c40

Maximum output
frequency

50.0

7.5

{Hz}

240 • Output frequency at 100% analog setpoint

• C11 is never exceeded

WARNING!

Consult motor/machine manufacturer before operating above rated frequency.
Overspeeding the motor/machine may cause damage to equipment and injury to
personnel!

Acceleration time 1

5.0

0.0

{s}

999 • C12 = frequency change 0 Hz...C11

• C13 = frequency change C11...0 Hz
• For S-ramp accel/decel, adjust c82

Deceleration time 1

5.0

0.0

{s}

999