Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

101

Programming and Parameters

Chapter 4

Utility File

Fil

e

Gr

oup

No.

Parameter Name & Description

Values

U

TIL

IT

Y

Co

nv

er

te

r Me

mor

y

090

[Param Access Lvl]
Selects the parameter display level.
0 (Basic) = Reduced parameter set.
1 (Advanced) = Full parameter set.

Default:

Options:

0

0
1

Basic

Basic
Advanced

091

[Reset to Defaults]
Resets parameters to factory defaults except parameters 093 [Language] and
090 [Param Access Lvl].
0 (Ready) = A new value may be entered.
1 (Factory) = Resets parameters to factory defaults.
2 (Low Voltage) = Resets parameters to factory defaults and configures parameters for a:

400/480V AFE unit for 400V operation.
600/690V AFE unit for 600V operation.

3 (High Voltage) = Resets parameters to factory defaults and configures parameters for a:

400/480V AFE unit for 480V operation.
600/690V AFE unit for 690V operation.

NOTE: The DC bus voltage must be present to set the voltage class.

Default:

Options:

0

0
1
2
3

Ready

Ready
Factory
Low Voltage
High Voltage

092

[Reset Meters]
Resets these selected meters (Motoring MWh, Regen MWh, and Elapsed Time) to zero.

Default:

Options:

0

0
1
2
3

Ready

Ready
Motoring MWh
Regen MWh
Elapsed Time

093

[Language]
Limited to English language only.

Default:

Options:

0

0
1

Not Selected

Not Selected
English

094

[Voltage Class]
Displays the last ‘Reset To Defaults’ operation.

Default:

Options:

Read Only

0 = Low Voltage
1 = High Voltage

Di

ag

n

os

ti

cs

095

[Cnvrtr Status 1]
Displays the present operating condition of the AFE.

Bit 0 (Ready) indicates all inhibits are cleared.
Bit 1 (Active) indicates the AFE is modulating.
Bit 2 (Motoring) indicates the AFE is running in motoring mode.
Bit 3 (Regenerating) indicates the AFE is regenerating power to the AC line.
Bit 4 (In Precharge) indicates the AFE is in precharging status.
Bit 5 (Droop Active) indicates that the droop function for AFE paralleling is activated.
Bit 6 (Alarm) indicates the AFE has detected an alarm.
Bit 7 (Faulted) indicates the AFE has detected a fault.
Bit 8 (At Reference) indicates the DC bus voltage is at the command value.
Bit 9 (Mot CurLim) indicates the AFE exceeds the current limit in motoring mode.
Bit 10 (Regen CurLim) indicates the AFE exceeds the current limit in regenerative mode.
Bit 11 (Cmd Delayed) indicates pending start command.
Bits 12…14 indicate the DC bus voltage reference selection.

Read Only

Bit
Definition

DC

Vo

lt

Re

fD2

DC

Vo

lt

Re

fD1

DC

Vo

lt

Re

fD0

Cm

d D

ela

yed

Re

gen C

urLim

Mot C

urLim

At

R

ef

er

en

ce

Fa

ul

te

d

Alar

m

D

roop A

ctiv

e

In Pr

ec

har

ge

Regener

ating

Mot

ori

ng

Ac

tive

Re

ad

y

Default

x

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

1 = Condition True
0 = Condition False
x = Reserved

Bits

Description

14 13 12

0
0
0
0
1
1
1
1

0
0
1
1
0
0
1
1

0
1
0
1
0
1
0
1

DC Volt Ref
Analog In1
Analog In2
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5