Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 123

Advertising
background image

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

123

Troubleshooting

Chapter 5

Figure 40 - AFE Start Sequence Troubleshooting Diagram

Ready to

switch on

Software initialize complete

Charging the DC link

with external charging circuit

Run command from I/O,

keypad or Fieldbus (depends

on the selected control)

Init

DC link voltage

> 0.8*DC nominal?

Yes

No

Input Contactor

Close through Digital Out1,

should be set = ‘Contact Ctrl’

Sychronizing

OK?

Sychronizing

tries

≥ 5

Yes

Yes

Ready to Run

(see P95 - [Cnvrtr Status1]

Ready bit = 1)

Synchronize

with input

Startup delay elapsed?

(see P087 - [Start Up Delay],

default = 0 secs)

Yes

No

No

Fault F10:

LineSyncFail

Input Contactor Ack

(Digital Input 4, should be

set = ‘Contactor Ack’; see

P102 - [Dig In Status] for

digital input status)

Yes

No

AFE Running

(Run LED is on)

Request to close

input contactor on

Digital In3?

Yes

No

Advertising