Frame 13 – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 53

Advertising
background image

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

53

AFE in IP21 Rittal Enclosure—Installation/Wiring

Chapter 2

Frame 13

The following figure shows a basic one-line diagram for an AFE Frame 13 in a
IP21 Rittal enclosure. The main component sections consist of the following
items:

AC Line Switchgear consisting of the input disconnect (Q0) and MCCB
motor-controlled circuit breaker (Q1)

LCL Filter (L1)

Precharge Circuit

AFE power structure (U1) with AFE control assembly

DC fuses (F2.1…F2.6)

Figure 23 - Basic One-line Diagram for an AFE Frame 13 in IP21 Rittal Enclosure

DC Bus
Output

L1

3 Phase

AC Input

L2

L3

PowerFlex

Active Front End System

Precharge

Circuit

R6.1

R6.2

+

-

AC Line

Switchgear

LCL Filter (L1)

AFE

Power Structure (U1)

DC

Fuses

U2

V2

W2

C1

C2

C3

C4

C5

C6

U1

V1

W1

Q1

Q0

Precharge

Fuses

Precharge

Contactor

Motor Protection

Relay

Q5

K6

F6

F2.1

F2.2

F2.3

F2.4

F2.5

F2.6

DC+

DC-

W

PE

PE

DC+

DC-

V

PE

DC+

DC-

U

PE

Advertising