I/o terminal blocks – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

Chapter 1

AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring

Table 5 - Recommended Control Wire for Digital I/O

Figure 20 - Door Control Box I/O Terminal Blocks and Jumpers

I/O Terminal Blocks

Table 6 - Door Control Box I/O Terminal Block Specifications for AFE in IP20 2500 MCC Style Enclosure

Type

Wire Type(s)

Description

Minimum
Insulation Rating

Unshielded

Per US NEC or applicable national or local code

300V, 60 °C
(140 °F)

Shielded

Multi-conductor shielded cable such as Belden
8770(or equivalent)

0.5 mm

2

(22 AWG),

3 conductor, shielded

J1

J2

J3

J4

J5

Components mounted on inside

of AFE enclosure (see

Figure 12

for location)

See

Table 6

below for door control box item number descriptions and specifications.

Door Control Box Components

X3 Term. No.

Default

Description

57 and 60

Remote momentary pulse of 0.4…1.0 sec. across these terminals starts
precharge in REM mode when terminals 58 and 61 are remotely closed.

58 and 61

These terminals must be remotely closed to start precharge. Opening
these terminals opens the main contactor K1.

63 and 64

Remotely closing these terminals resets an AFE fault.

65 and 66

AFE run signal to the inverter enable input.

400 and 480

480

Control input voltage setting.

600 and 690

690

For jumper configurations,
see

Table 8 on page 45

.

(X3 Terminals)

No.

Name

Description

Wire Size Range

(1)

(1) Maximum/minimum that the terminal block will accept - these are not recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

Analog I/O

Analog I/O Signals

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.2 N•m
1.8 lb•in

0.2 N•m
1.8 lb•in

Digital Inputs

Digital Input Signals

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.2 N•m
1.8 lb•n

0.2 N•m
1.8 lb•in

Digital Outputs

Digital Out Relays

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.5 N•m
4.5 lb•in

0.5 N•m
4.5 lb•in

Control Terminal

Customer input and
output control

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.8 N•m
7.1 lb•in

0.8 N•m
7.1 lb•in

Advertising