I/o terminal blocks – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

Chapter 1

AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring

Table 5 - Recommended Control Wire for Digital I/O

Figure 20 - Door Control Box I/O Terminal Blocks and Jumpers

I/O Terminal Blocks

Table 6 - Door Control Box I/O Terminal Block Specifications for AFE in IP20 2500 MCC Style Enclosure

Type

Wire Type(s)

Description

Minimum
Insulation Rating

Unshielded

Per US NEC or applicable national or local code

—

300V, 60 °C
(140 °F)

Shielded

Multi-conductor shielded cable such as Belden
8770(or equivalent)

0.5 mm

2

(22 AWG),

3 conductor, shielded

➋

➌

J1

J2

J3

J4

J5

➍

Components mounted on inside

of AFE enclosure (see

Figure 12

for location)

See

Table 6

below for door control box item number descriptions and specifications.

Door Control Box Components

X3 Term. No.

Default

Description

57 and 60

—

Remote momentary pulse of 0.4…1.0 sec. across these terminals starts
precharge in REM mode when terminals 58 and 61 are remotely closed.

58 and 61

—

These terminals must be remotely closed to start precharge. Opening
these terminals opens the main contactor K1.

63 and 64

—

Remotely closing these terminals resets an AFE fault.

65 and 66

—

AFE run signal to the inverter enable input.

400 and 480

480

Control input voltage setting.

600 and 690

690

For jumper configurations,
see

Table 8 on page 45

.

➊

(X3 Terminals)

No.

Name

Description

Wire Size Range

(1)

(1) Maximum/minimum that the terminal block will accept - these are not recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

➊

Analog I/O

Analog I/O Signals

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.2 N•m
1.8 lb•in

0.2 N•m
1.8 lb•in

➋

Digital Inputs

Digital Input Signals

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.2 N•m
1.8 lb•n

0.2 N•m
1.8 lb•in

➌

Digital Outputs

Digital Out Relays

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.5 N•m
4.5 lb•in

0.5 N•m
4.5 lb•in

➍

Control Terminal

Customer input and
output control

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.8 N•m
7.1 lb•in

0.8 N•m
7.1 lb•in

Advertising