Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 82

Advertising
background image

82

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

Chapter 3

Startup

4.

Verify that the control power voltage is correct.

5.

When DC disconnects are used for each inverter, verify that the
disconnect levers for all inverters are set to off.

6.

Set the REM-MAN-AUTO switch to MAN.

7.

Set the OFF-ON-START switch to OFF.

Programming the AFE

1.

Turn the AFE circuit breaker handle to on.

2.

Set parameter 091 [Reset To Defaults] to the appropriate setting for your
installation.

3.

Use the HIM to enter the Assisted Start-up procedure.

Figure 37 - Active Front End Start-up Procedure Menu

091

[Reset to Defaults]
Resets parameters to factory defaults except parameters 093 [Language] and
090 [Param Access Lvl].
0 (Ready) = A new value may be entered.
1 (Factory) = Resets parameters to factory defaults.
2 (Low Voltage) = Resets parameters to factory defaults and configures parameters for a:

400/480V AFE unit for 400V operation.
600/690V AFE unit for 600V operation.

3 (High Voltage) = Resets parameters to factory defaults and configures parameters for a:

400/480V AFE unit for 480V operation.
600/690V AFE unit for 690V operation.

NOTE: The DC bus voltage must be present to set the voltage class.

Default:
Options:

0
0
1
2
3

Ready
Ready
Factory
Low Voltage
High Voltage

Step

Example LCD Display

a. In the Main Menu, use the

or

key to scroll to ‘Start Up’.

b. Press the

(Enter) key.

F-> Stopped

Auto

0.0

Volt

Main Menu:
Memory Storage

Start Up

Preferences

Sets Input

Voltage

Input Voltage

Select

Startup

Defines

Configurable

Alarms and Faults

Alarm/Flt Cnfg

Sets Current

and

Power Limits

Limits

Sets the

DC Bus Voltage

Reference

DC Bus Ctrl

Start/Stop/I/O

Configures

Digital Inputs

(including Run),

Digital Outputs,

and Analog Outputs

Done /
Exit

Main Menu: