Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 141

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
141
Supplemental Information
Appendix A
Logic Status Word for PowerFlex 700/700H/700S Drives
The AFE reference is the commanded bus voltage (for example, a value of 6000
represents 600.0V DC). The feedback value is the bus voltage measured in the
AFE.
Logic Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Status
Description
x
Ready
0 = Not Ready
1 = Ready
x
Active
0 = Not Active
1 = Active
x
Motoring
0 = Not Motoring
1 = Motoring
x
Regenerating
0 = Not Regenerating
1 = Regenerating
x
In Precharge
0 = Not In Precharge
1 = In Precharge
x
Droop Active
0 = Not Droop Active for AFE
Paralleling
1 = Droop Active for AFE Paralleling
x
Alarm
0 = No Alarm
1 = Alarm
x
Faulted
0 = Not Faulted
1 = Faulted
x
At Reference
0 = Not At Reference
1 = At Reference
x
Mot CurLim
0 = Not Exceeding Current Limit in
Motoring Mode
1 = Exceeding Current Limit in
Motoring Mode
x
Regen CurLim
0 = Not Exceeding Current Limit in
Regenerative Mode
1 = Exceeding Current Limit in
Regenerative Mode
x
Cmd Delayed
0 = Condition False
1 = Condition True
x
DCVoltRefID0
x
DCVoltRefID1
x
DCVoltRefID2
x
Reserved
Bits
Description
14
13
12
0
0
0
= DC Volt Ref
0
0
1
= Analog In 1
0
1
0
= Analog In 2
0
1
1
= DPI Port 1
1
0
0
= DPI Port 2
1
0
1
= DPI Port 3
1
1
0
= DPI Port 4
1
1
1
= DPI Port 5