The output of the DC voltage controller is the active current reference, which is
compared to the measured active current. The error between them is the input
for the active current controller. The output of the active current controller
changes the modulation index and controls the inverter voltage.

The reactive current reference can be used for reactive power compensation. A
positive reactive current reference indicates inductive and a negative reactive
current reference indicates capacitive reactive power compensation. The default
value of the reactive current reference parameter is zero. The set value of the
reactive current reference is compared to its measured value and the error is fed to
the PI regulator. The PI regulator is also referred to as the ‘synchronizing
controller’ because its function is to keep the inverter synchronized with line
supply. The frequency reference to the AFE is derived from the reactive current
controller output. Normally the active current Kp, active current Ki, reactive
current Kp, and reactive current Ki default values of the two current controllers
are satisfactory with the standard LCL filter, and should not be changed.

Figure 3 - AFE Block Diagram

I

L1

3

2

_

_

_

PI

PI

PI

PD

Park Transform

DC Volt Measured

DC Volt Reference

Reactive Current Ref

Reactive Current

Active Current Ref

Modulation Index

Active Current

Freq Reference

DC Volt Kp

DC Volt Ki

Reactive Curr Kp

Reactive Curr Ki

Active Curr Kp

Active Curr Ki

Cartesian

Modulator Voltage Angle

Reactive Current

Active Current

Polar

I Alpha

I Beta

I

L2

I

L3

Advertising