Frame 13 power structure – Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 71
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
71
AFE in IP21 Rittal Enclosure—Installation/Wiring
Chapter 2
Frame 13 Power Structure
The AFE Frame 13 power structure in the IP21 Rittal enclosure contains
common mode capacitors that must be removed
. These capacitors are located
on the Phase V (center) module of the power structure. Use the following
procedure to remove these capacitors from the AFE Frame 13 power structure.
1.
Locate the common mode capacitors on the Phase V module of the Frame
13 power structure.
2.
Remove the common mode capacitors.
a. Disconnect the two black wires.
b. Unscrew and remove the capacitor assembly consisting of two
capacitors on a small metal bracket.
Location of Common Mode
Capacitors on Phase V Module of
Frame 13 AFE Power Structure
Phase V Module of Frame 13
Power Structure
Close-up View of Common
Mode Capacitors on Phase V
Module of Frame 13 AFE
Power Structure
Disconnect Wires and
Unscrew Capacitor Assembly
Close-up View of Common
Mode Capacitor Assembly