Inputs & outputs file – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 109

Advertising
background image

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

109

Programming and Parameters

Chapter 4

Inputs & Outputs File

Fil

e

Gr

oup

No.

Parameter Name & Description

Values

INPUT

S &

OUTPUT

S

An

al

og

In

pu

ts

200

[Anlg In Config]
Selects the mode for the analog inputs.

201

[Analog In 1 Hi]
Sets the highest input value to the Analog Input 1 scaling block.
Parameter 200 [Anlg In Config] defines if this input will be -/+10V or 4-20 mA.

Default:

Min/Max:

Units:

10.000V

4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V

202

[Analog In 1 Lo]
Sets the lowest input value to the Analog Input 1 scaling block.
Parameter 200 [Anlg In Config] defines if this input will be -/+10V or 4-20 mA.

Default:

Min/Max:

Units:

0.000V

4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V

203

[Analog In 1 Loss]
Selects the AFE action when an analog signal loss is detected. Signal loss is defined as an analog signal
less than 1V or 2 mA. The signal loss event ends and normal operation resumes when the input signal
level is greater than or equal to 1.5V or 3 mA.

Default:

Options:

0

0
1
2
3
4

Disabled

Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi

204

[Analog In 2 Hi]
Sets the highest input value to the Analog Input 2 scaling block.
Parameter 200 [Anlg In Config] defines if this input is -/+10V or 4-20 mA.

Default:

Min/Max:

Units:

10.000V

4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V

205

[Analog In 2 Lo]
Sets the lowest input value to the Analog Input 2 scaling block.
Parameter 200 [Anlg In Config] defines if this input is -/+10V or 4-20 mA.

Default:

Min/Max:

Units:

0.000V

4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V

206

[Analog In 2 Loss]
Selects the AFE action when an analog signal loss is detected. Signal loss is defined as an analog signal
less than 1V or 2 mA. The signal loss event ends and normal operation resumes when the input signal
level is greater than or equal to 1.5V or 3 mA.

Default:

Options:

0

0
1
2
3
4

Disabled

Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi

Anal

og

O

utput

s

207

[Anlg Out Config]
Selects the mode for the analog outputs.

Important: Make sure the jumpers are in the correct position or the output will be wrong:

J3 = Analog Output 1; J4 = Analog Output 2
Position AB = Current; Position BC = Voltage 0-10V (default); Position CD = Voltage -/+10V

Bit
Definition

An2 (0 = V

, 1

= m

A)

An1 (0 = V

, 1

= m

A)

Default

x

x

x

x

x

x

x

x

x

x

x

x

x

x

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

1 = Current
0 = Voltage
x = Reserved

Bit
Definition

An2 (0 = V

, 1 = m

A)

An1 (0 = V

, 1 = m

A)

Default

x

x

x

x

x

x

x

x

x

x

x

x

x

x

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

1 = Current
0 = Voltage
x = Reserved