AFE in IP21 Rittal Enclosure—Installation/Wiring

Figure 27 - Typical Grounding Example for AFE Frame 13 in IP21 Rittal Enclosure

Safety Ground - PE

This is the safety ground for the AFE that is required by code. This point must be
connected to adjacent building steel (girder or joist), a floor ground rod or bus
bar (see above). Grounding points must comply with national and local industrial
safety regulations and/or electrical codes.

Shield Termination - SHLD

The Shield terminal (

Figure 30

or

Figure 31

) provides a grounding point for the

AFE cable shield. It must be connected to an earth ground by a separate
continuous lead. The drive cable shield must be connected to this terminal on
the AFE end and the drive frame on the drive end. Use a shield terminating or
EMI clamp to connect the shield to this terminal.

PE

Customer wiring required to
connect the AFE to the drive.

SHLD

PowerFlex AFE Frame 13

PowerFlex 750-Series Drive or
PowerFlex 7-Class Drive
(PowerFlex 700S Frame 10 drive shown)

To Line PE

DC+
DC-

DC+
DC-

PE

PE

R (L1), S (L2), T (L3)

U (T1), V (T2), W (T3)