Safety ground - pe, Shield termination - shld, Safety ground - pe shield termination - shld – Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 60

60
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 2
AFE in IP21 Rittal Enclosure—Installation/Wiring
Figure 27 - Typical Grounding Example for AFE Frame 13 in IP21 Rittal Enclosure
Safety Ground - PE
This is the safety ground for the AFE that is required by code. This point must be
connected to adjacent building steel (girder or joist), a floor ground rod or bus
bar (see above). Grounding points must comply with national and local industrial
safety regulations and/or electrical codes.
Shield Termination - SHLD
The Shield terminal (
) provides a grounding point for the
AFE cable shield. It must be connected to an earth ground by a separate
continuous lead. The drive cable shield must be connected to this terminal on
the AFE end and the drive frame on the drive end. Use a shield terminating or
EMI clamp to connect the shield to this terminal.