AFE in IP21 Rittal Enclosure—Installation/Wiring

Mounting Considerations

When mounting the Active Front End, consider the following information.

Operating Temperatures

Minimum Mounting Clearances

Frame 10 in IP21 Rittal Enclosure

Frame
Size

Surrounding Air Temperature

(2)

(2) For an AFE in the IP21 Rittal enclosure, this means air surrounding the module.

Minimum Air Flow

Normal Duty

Heavy Duty

Power Module

LCL Filter

10

0…40 °C
(32…104 °F)

0…40 °C
(32…104 °F)

1400 m

3

/hr (824 cfm)

1100 m

3

/hr (647 cfm)

13

(1)

(1) The Frame 13 690V AFE has only Normal Duty operation at nominal rated power and maximum ambient temperature at 35 °C.

4200 m

3

/hr (2472 cfm)

1300 m

3

/hr (765 cfm)

200 mm

(7.87 in.)

Height Clearance

400 mm

(15.7 in.)

Door Swing Clearance

600 mm

(23.6 in.)

Door Swing Clearance

TOP VIEW

FRONT VIEW

50 mm

(2.0 in.)

Clearance to Wall

50 mm
(2.0 in.)
Clearance to Wall