Mounting considerations, Operating temperatures, Minimum mounting clearances – Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 56: Operating temperatures minimum mounting clearances

56
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 2
AFE in IP21 Rittal Enclosure—Installation/Wiring
Mounting Considerations
When mounting the Active Front End, consider the following information.
Operating Temperatures
Minimum Mounting Clearances
Frame 10 in IP21 Rittal Enclosure
Frame
Size
Surrounding Air Temperature
(2)
(2) For an AFE in the IP21 Rittal enclosure, this means air surrounding the module.
Minimum Air Flow
Normal Duty
Heavy Duty
Power Module
LCL Filter
10
0…40 °C
(32…104 °F)
0…40 °C
(32…104 °F)
1400 m
3
/hr (824 cfm)
1100 m
3
/hr (647 cfm)
13
(1)
(1) The Frame 13 690V AFE has only Normal Duty operation at nominal rated power and maximum ambient temperature at 35 °C.
4200 m
3
/hr (2472 cfm)
1300 m
3
/hr (765 cfm)
200 mm
(7.87 in.)
Height Clearance
400 mm
(15.7 in.)
Door Swing Clearance
600 mm
(23.6 in.)
Door Swing Clearance
TOP VIEW
FRONT VIEW
50 mm
(2.0 in.)
Clearance to Wall
50 mm
(2.0 in.)
Clearance to Wall