Cable trays and conduit – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 33

Advertising
background image

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

33

AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring

Chapter 1

Cable Trays and Conduit

If cable trays or large conduits are to be used, refer to guidelines presented in
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC
Drives, publication DRIVES-IN001.

Selecting and Verifying Control Transformer Voltage

The control transformer in the AFE is used to match the input AC line voltage of
the AFE in an IP20 2500 MCC Style enclosure to the 230V and 120V control
voltage.

Verify that the control voltage is set appropriately for the supplied AC line
voltage. If necessary, change the control voltage using this procedure.

1.

Locate the X3 terminal block (

Figure 12

).

Figure 12 - X3 Terminal Block Location for AFE in IP20 2500 MCC Style Enclosure

ATTENTION: To avoid a possible shock hazard caused by induced voltages,
unused wires in the conduit must be grounded at both ends. For the same reason,
if a drive sharing a conduit is being serviced or installed, all drives using this
conduit must be disabled. This helps minimize the possible shock hazard from
‘cross coupled’ motor leads.

X3 Terminal
Block Location

Frame 10

(shown with enclosure

doors removed)

FRONT VIEW

FRONT VIEW

Frame 13

(shown with enclosure

doors removed)

X3 Terminal
Block Location

X3 Terminal

Block Location