AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring

Mounting Considerations

When mounting the Active Front End, consider the following information.

Operating Temperatures

Minimum Mounting Clearances

Frame 10 in IP20 2500 MCC Style Enclosure

Frame
Size

Surrounding Air Temperature

(2)

(2) For an AFE in the IP20 2500 MCC Style enclosure, this air means surrounding the outside of the enclosure.

Minimum Air Flow

Normal Duty

Heavy Duty

Power Module

LCL Filter

10

0…40 °C
(32…104 °F)

0…40 °C
(32…104 °F)

1400 m

3

/hr (824 cfm)

1100 m

3

/hr (647 cfm)

13

(1)

(1) The Frame 13 690V AFE has only Normal Duty operation at nominal rated power and maximum ambient temperature at 35 °C.

4200 m

3

/hr (2472 cfm)

1300 m

3

/hr (765 cfm)

50 mm

(2.0 in.)

Clearance to Wall

50 mm
(2.0 in.)
Clearance to Wall

565.9 mm

(22 in.)

Door Swing Clearance

200 mm

(7.87 in.)

Height Clearance

TOP VIEW

FRONT VIEW