Mounting considerations, Operating temperatures, Minimum mounting clearances – Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 26: Operating temperatures minimum mounting clearances

26
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 1
AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring
Mounting Considerations
When mounting the Active Front End, consider the following information.
Operating Temperatures
Minimum Mounting Clearances
Frame 10 in IP20 2500 MCC Style Enclosure
Frame
Size
Surrounding Air Temperature
(2)
(2) For an AFE in the IP20 2500 MCC Style enclosure, this air means surrounding the outside of the enclosure.
Minimum Air Flow
Normal Duty
Heavy Duty
Power Module
LCL Filter
10
0…40 °C
(32…104 °F)
0…40 °C
(32…104 °F)
1400 m
3
/hr (824 cfm)
1100 m
3
/hr (647 cfm)
13
(1)
(1) The Frame 13 690V AFE has only Normal Duty operation at nominal rated power and maximum ambient temperature at 35 °C.
4200 m
3
/hr (2472 cfm)
1300 m
3
/hr (765 cfm)
50 mm
(2.0 in.)
Clearance to Wall
50 mm
(2.0 in.)
Clearance to Wall
565.9 mm
(22 in.)
Door Swing Clearance
200 mm
(7.87 in.)
Height Clearance
TOP VIEW
FRONT VIEW