Monitor file – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 95

Advertising
background image

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

95

Programming and Parameters

Chapter 4

Monitor File

Fil

e

Gr

oup

No.

Parameter Name & Description

Values

MON

IT

O

R

Meterin

g

001

[Input Voltage]
Displays the incoming supply voltage, only when the AFE is in the Run state.

Default:

Min/Max:
Units:

Read Only

0.0/1000.0V AC
0.1V AC

002

[AC Line Freq]
Displays the supply frequency. The sign indicates the phase order, only when the AFE is in the Run state.

Default:

Min/Max:
Units:

Read Only

-63.0/63.0 Hz
0.1 Hz

003

[Total Current]
Displays the total AC input current present at L1, L2, and L3 inputs.

Default:

Min/Max:
Units:

Read Only

0.0/[Rated Amps] x 2
0.1 Amps

004

[Active Current]
Displays the amount of AC input current that is in phase with the AC input fundamental voltage
component. Positive value indicates motoring; negative value indicates regeneration.

Default:

Min/Max:
Units:

Read Only

+/- [Rated Amps] x 2
0.1 Amps

005

[Reactive Current]
Displays the amount of AC input current that is out of phase with the AC input fundamental voltage
component. Positive value indicates inductive current; negative value indicates capacitive current.

Default:

Min/Max:
Units:

Read Only

+/- [Rated Amps] x 2
0.1 Amps

006
007
008

[Input Current R]
[Input Current S]
[Input Current T]
Displays the RMS value of the L1, L2, and L3 phase AC input current.

Default:

Min/Max:
Units:

Read Only

0.0/6553.5 Amps
0.1 Amps

009

[I Imbalance]
Displays the current imbalance calculated between phases L1, L2, and L3.

The RMS current for each phase is calculated by summing the instantaneous current squared as sampled
at the PWM peak and valley, and then taking the square root of the sum every AC line cycle.

The imbalance is then evaluated every AC line cycle by first finding the largest, smallest, and average
phase current. Two equations are then used to calculate the value displayed:

Based_on_Largest = (Largest - Average) x 100 / Average
Based_on_Largest = (Largest - Average) x 100 / Average

The equation that gives the higher value is used for the display.

Default:

Min/Max:
Units:

Read Only

0.0/100.0%
0.1%

010

[Ground Current]
Displays the ground current measured by summing the three input phase currents.

Default:

Min/Max:
Units:

Read Only

0.0/[Rated Amps] x 2
0.1 Amps

011

[DC Bus Volt]
Displays the filtered DC bus voltage. The filter time constant is 32 milliseconds.

Default:

Min/Max:
Units:

Read Only

0.0/Based on Unit Rating
0.1V DC

012

[DC Bus Current]
Displays the DC bus current. Positive value indicates motoring; negative value indicates regeneration.

Default:

Min/Max:
Units:

Read Only

+/- Based on Unit Rating
0.1 Amps

013

[AC Line kW]
Displays the real power on the AC side. Positive value indicates motoring; negative value indicates
regeneration.

Default:

Min/Max:
Units:

Read Only

+/- Based on Unit Rating
0.1 kW

014

[AC Line kVar]
Displays the reactive power on the AC line.

Default:

Min/Max:
Units:

Read Only

+/- Based on Unit Rating
0.1 kVar

015

[AC Line kVA]
Displays the apparent power on the AC line.

Default:

Min/Max:
Units:

Read Only

0.0/Based on Unit Rating
0.1 kVA

016

[Power Factor]
Displays the power factor. Positive value indicates motoring power; negative sign indicates regenerative
power.

Default:

Min/Max:
Units:

Read Only

+/-1.00
0.01

017

[Heatsink Temp]
Displays the measured heatsink temperature.

Default:

Min/Max:
Units:

Read Only

0/200 °C
1 °C

32

32

32

32

32

32

32

Advertising