Programming and Parameters

Chapter 4

UTILIT

Y

Fa

u

lt

s

120

[Fault Config]
Enables/disables annunciation of the listed faults.

121

[Fault Clear]
Resets a fault and clears the fault queue.
0 (Ready) = A new value may be entered.
1 (Clear Faults) = A fault is reset.
2 (Clr Fault Que) = The fault queue is cleared.

Default:

Options:

0

0
1
2

Ready

Ready
Clear Faults
Clr Fault Que

122

[Fault Clear Mode]
Enables/disables a fault reset (clear faults) attempt from any source. This does not apply to fault codes which
are cleared indirectly through other actions.

Default:

Options:

1

0
1

Enabled

Disabled
Enabled

123

[Power Up Marker]
Displays the elapsed hours since initial AFE power up. This value rolls over to ‘0’ after the AFE has been powered
on for more than the maximum value shown. For relevance to most recent power up, see parameters
128…131 [Fault x Time].

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295 Hr
0.0001 Hr

124
126
128
130

[Fault 1 Code]
[Fault 2 Code]
[Fault 3 Code]
[Fault 4 Code]
Displays a code that represents the fault that tripped the AFE. The codes appear in these parameters in the
order they occur (parameter 124 [Fault 1 Code] = the most recent fault).

Default:

Min/Max:
Units:

Read Only

0/65535
None

125
127
129
131

[Fault 1 Time]
[Fault 2 Time]
[Fault 3 Time]
[Fault 4 Time]
Displays the time between initial AFE power up and the occurrence of the associated trip fault. The time shown
by these parameters can be compared to parameter 123 [Power Up Marker] for the time from the most recent
power up. Therefore, [Fault x Time] - [Power Up Marker] = Time difference to the most recent power up. A
negative value indicates the fault occurred before the most recent power up. A positive value indicates the fault
occurred after the most recent power up.

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295 Hr
0.0001 Hr

132

[Contact Off Cnfg]
Configures faults that will force the main contactor off in case of fault. This is only possible if the precharge
contactor is off or controlled over the network (Digital output selection) and the AFE is supplied by an external
24V DC power supply.
This provides an option to protect the AFE when the AFE is faulted, modulating is stopped, and the motoring
current can still flow through the IGBT diode.

133

[Cnvrtr OL Factor]
Sets the operating level for the AFE overload.
(AFE rated current) x (AFE OL Factor) = Operating Level

Default:

Min/Max:
Units:

1.00

0.50/1.50
None

Fil

e

Gr

oup

No.

Parameter Name & Description

Values

Bit
Definition

Au

to

Re

se

tL

im

Ov

er

lo

ad

Lin

eS

yncF

ai

l

DC Unde

rV

olt

Default

x

x

x

x

x

x

x

x

x

x

0

0

0

x

0

x

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

1 = Enabled
0 = Disabled
x = Reserved

32

32

Bit
Definition

All F

ault

LC

L O

ve

rT

em

p

He

at

si

nk

O

vT

p

Ov

er

lo

ad

AC

O

ve

rCu

rr

IGB

TO

ver

Te

mp

DC O

ve

rV

olt

Au

xi

lia

ry

In

Default

x

x

x

x

x

x

0

0

0

0

x

0

0

0

x

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

1 = Enabled Contactor Off command from fault*
0 = Disabled Contactor Off command from fault
x = Reserved

* If enabled, the auto restart function will be disabled.