AFE in IP21 Rittal Enclosure—Installation/Wiring

5.

All shielded cables must terminate with proper shielded connector.

6.

Motor cables of DC input drives used with the AFE must be shielded cable
wire with a coverage of 75% or more, or must be inside metal conduit or
have shielding/cover with equivalent attenuation.