Chapter 1

AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring

Table 7 - Door Control Box I/O Terminal Designations for AFE in IP20 2500 MCC Style Enclosure

ATTENTION: For the AFE in the IP20 2500 MCC Style enclosure, Digital Inputs
1, 3, 4, and 5, and Digital Outputs 1 and 2 are factory wired and programmed
to operate from the controls on the front of the enclosure. Digital Output 3 is
programmable and factory wired for +24V DC only. Do not change the wiring
and programming for those digital inputs and outputs, or it will result in
malfunction of the system.

No.

Signal

Factory Default

Description

1

Analog In 1 (–)

(1)

(1) Important: Input must be configured with a jumper. AFE damage can occur if jumper is not installed properly. See

Analog I/O

Configuration on page 45

.

(2)

(2) These inputs/outputs are dependant on a number of parameters.

Isolated

(3)

, bipolar, differential, 9 bit & sign,

88k ohm input impedance. A jumper (see

Table 8

) selects 0-10V, ±10V, or 4-20 mA.

Default: 0-10V (Ri = 200k ohm), 4-20 mA
(Ri = 100 ohm).

(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode

immunity.

2

Analog In 1 (+)

(1)

3

Analog In 2 (–)

(1)

4

Analog In 2 (+)

(1)

5

–10V Pot Reference

2k ohm min, 10 mA max load, 1% accuracy

6

Pot Common (GND)

For (+) and (–) 10V pot references

7

+10V Pot Reference

2k ohm min, 10 mA max load, 1% accuracy

8

Analog Out 1 (+)

(2)

Bipolar (current out is not bipolar), 9 bit and
sign, 2k ohm min load. A jumper (see

Table 8

) selects 0-10V, ±10V, or 4-20 mA.

9

Analog Out Common

10

Analog Out 2 (+)

11

Digital In 1

RunCmd

24V DC - Opto isolated (250V)
Low State: less than 5V DC
High State: greater than 20V DC, 11.2 mA
DC
Enable: Digital Input 6 is jumper selectable
for HW Enable.
On-Time: < 16.7 ms, Off-Time < 1 ms

12

Digital In 2

Ext. Reset

13

Digital In 3

Enable Mcont

14

Digital In 4

Contactor Ack

15

Digital In 5

LCL Temp

16

Digital In 6/Hardware
Enable, see

page 46

17
18

Digital In Common

Allows source or sink operation

19

+24V DC

(4)

(4) 150 mA maximum load. Can be used to provide control power from an external 24V source when main power is not applied.

Unit supplied logic input power

20

24V Common

(4)

Common for internal power supply

21

Digital Out 1 – N.C.

(5)

(5) Contacts in un-powered state. Any relay programmed as Fault or Alarm energizes (pick up) when power is applied to the AFE, and

de-energizes (drop out) when a fault or alarm exists. Relays selected for other functions energize only when that condition exists
and de-energizes when the condition is removed.

Contact Ctrl

Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10 mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10 mA
NOTE: See the Attention above this table
for more details.

22

Digital Out 1 Common

23

Digital Out 1 – N.O.

(5)

24

Digital Out 2 – N.C.

(5)

Fault

25

Digital Out 2/3 Com.

26

Digital Out 3 – N.O.

(5)

(6)

(6) When this output is configured as active, it can be wired to the Enable input of the connected drives to prevent the AFE from

supplying power when the AFE is not running.

Active

1

10

20

21

26