Ac input fuse and circuit breaker ratings, Dc bus output fuse ratings – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 130

Advertising
background image

130

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

Appendix A

Supplemental Information

Fusing and Circuit Breakers
for AFE in IP21 Rittal
Enclosure

AC Input Fuse and Circuit Breaker Ratings

The tables in this section provide the recommended AC input line fuses and
circuit breakers. The AFE in a IP21 Rittal enclosure includes the recommended
MCCB (Motor-Controlled Circuit Breaker).

400/480 Volt AC Fusing and MCCB Ratings

600/690 Volt AC Fusing and MCCB Ratings

DC Bus Output Fuse Ratings

DC Bus Output fusing must be used for short circuit protection. The tables in
this section provide the ratings of the DC Bus Output fuses used for the AFE in a
IP21 Rittal enclosure.

465-800 Volt DC Fusing

640-1100 Volt DC Fusing

Frame
Size

Fuse Ratings

MCCB Ratings

Amps

Bussman Type

(1)

(1) Suitable for replacement fuse.

Ferraz Shawmut Type

Amps

ABB Type

10

800

NH3UD69V800PV

630

T5H630FF3LS

1000

170M6277

13

2200

PC44UD75V22CTQ

1600

T7516FF3PR231LS

1000

(3 per phase)

170M6277

Frame
Size

Fuse

MCCB Ratings

Amps

Bussman Type

(1)

(1) Suitable for replacement fuse.

Ferraz Shawmut Type

Amps

ABB Type

10

700

PC73UD13C630PA

400

T5H400LS

700

170M6305

13

1800

PC84UD12C18CTQ

1600

T7516FF3PR231LS

700

(3 per phase)

170M6305

Frame
Size

Fuse

Amps

Bussman Type

(1)

(1) Suitable for replacement fuse.

Ferraz Shawmut Type

10

1100

PC73UD95V11CTF

1250

170M6566

13

2400

PC84UD11C24CTQ

1250

(2 per phase)

170M6566

Frame
Size

Fuse

Amps

Bussman Type

(1)

(1) Suitable for replacement fuse.

Ferraz Shawmut Type

10

630

PC73UD13C630TF

700

170M6305

13

2000

PC84UD11C20CTQ

1000

(2 per phase)

170M8510