Frame 10 Power Structure
The AFE Frame 10 power structure in the IP21 Rittal enclosure contains
common mode capacitors that must be removed
. Use the following procedure
to remove these capacitors from the AFE Frame 10 power structure.
1.
Locate the common mode capacitors on the Frame 10 power structure.
2.
Remove the common mode capacitors.
a. Disconnect the two black wires.
b. Unscrew and remove the capacitor assembly consisting of two
capacitors on a small metal bracket.