Frame 10 or frame 13 power structure, Using the afe with powerflex drives, Control wiring – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 40: Using the afe with powerflex drives control wiring, Figure 19 on

Advertising
background image

40

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

Chapter 1

AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring

Figure 19 - AFE Frame 13 LCL Filter Common Mode Capacitor Jumper Locations

Frame 10 or Frame 13 Power Structure

Using the AFE with
PowerFlex Drives

When the Active Front End is used with drives that have common mode
capacitors (for example, PowerFlex 7-Class or PowerFlex 750-Series drives), the
common mode capacitors of these drives must be disconnected. See the
documentation for the respective drives.

When supplying power to PowerFlex drives of different frame sizes on the same
DC bus, additional bus capacitance may be needed. For details, see Drives in
Common Bus Configurations, publication DRIVES-AT002.

Control Wiring

The AFE in a IP20 2500 MCC Style enclosure is factory wired and programmed
to operate from the operator switches on the front of the enclosure. See

Table 7

and

Figure 21

for I/O terminal designations. Only when customized (or remote)

Remove Three
Jumpers

Remove Three
Jumpers

FRONT VIEW

OF LCL FILTER

IMPORTANT

The Frame 10 or Frame 13 AFE in a IP20 2500 MCC Style enclosure is shipped
from the factory with the common mode capacitors removed so the user need
not do this. However, when a power structure is replaced, the common mode
capacitors in the new power structure must be removed by the user prior
to installation
. For instructions to do this, see

Frame 10 Power Structure on

page 70

or

Frame 13 Power Structure on page 71

.