Chapter 5

Troubleshooting

13

Ground Fault

A current path to earth ground exists that is greater
than the parameter 082 [Ground I Lvl] value. The
current must appear for 800 milliseconds before the
unit will fault.

Check the cables.

14

Converter Flt

A hardware problem exists in the power structure.

1. Cycle the power.

2. Contact Technical Support (see

page 124

).

3. If the problem persists, replace the converter

unit.

17

LineSync Fail


One input line phase is missing.

1. Check all user-supplied fuses.

2. Check the AC input line voltage.

19

Unbalanced PU

An imbalance between the power modules exists
(paralleled units - only Frame 13).

1. Check for DC voltage imbalance between the

power modules.

2. Check for current input imbalance between

the power modules.

21

Phase Loss

There is zero current in one of the three phases.

Check supply voltage, fuses, and cable.

29

Anlg In Loss


An analog input is configured to fault on a signal loss.
A signal loss has occurred. Configure this fault with
parameter [Anlg In x Loss].

1. Check parameter settings.

2. Check for broken/loose connections at the

inputs.

30

MicroWatchdog

A microprocessor watchdog timeout has occurred.

1. Cycle the power.

2. Replace the Main Control board.

31

IGBT Temp Hw

The drive output current has exceeded the
instantaneous current limit.

1. Check for an excess load.

2. Contact Technical Support (see

page 124

).

32

Fan Cooling

Fan is not energized at start command.

1. Check the status of parameter 097 [Cnvrtr

Alarm 1] bit 5 (LCL Fan Stop). If set to ‘1’, check
the fan on the LCL Filter. If set to ‘0’, check the
fan on the converter.

2. If the LCL Filter fan is not operating, check its

DC power supply.

33

AutoReset Lim

The AFE unsuccessfully attempted to reset a fault and
resumed running for the programmed number in
parameter 053 [Auto Rstrt Tries]. You can enable/
disable this fault with parameter 120 [Fault Config].

Correct the cause and manually clear the fault.

34

CAN Bus Flt

A sent message was not acknowledged.

1. Cycle the power.

2. Replace the Main Control board.

35

Application

Problem in application software with task overload.

Contact Technical Support (see

page 124

).

37

HeatsinkUndTp

The ambient temperature is too low.

Raise the ambient temperature.

44

Device Change

The new power unit or option board installed is a
different type.

Clear the fault and reset the AFE to the factory
defaults.

45

Device Add

A new option board was added.

Clear the fault.

47

NvsReadChksum

There was an error reading parameters 019
[Motoring MWh], 020 [Regen MWh], and 021
[Elapsed Run Time] from EEPROM.

1. Cycle the power.

2. Replace the Main Control board.

54

Zero Divide

This event occurred because a mathematical function
had a dividend of zero.

1. Cycle the power.

2. Replace the Main Control board.

58

Start Prevent

Startup has been prevented.

1. Cancel prevention of startup if this can be

done safely.

2. Remove Run Request.

65

I/O Removed

An I/O option board has been removed.

Clear the fault.

Table 21 - Fault/Alarm Types, Descriptions, and Actions (Continued)

No.

Name

Fa

u

lt

Alarm

Description

Action (if appropriate)