Chapter 4

Programming and Parameters

INPU

TS & OUTPUT

S

An

al

og O

utput

s

208

[Anlg Out Absolute]
Selects whether the signed value or absolute value of a parameter is used before being scaled to drive the analog
output.

209

[Analog Out1 Sel]
Selects the source for Analog Output 1.

Default:

Options:

0 = Input Volt

See Table

210

[Analog Out1 Hi]
Sets the Analog Output 1 value when the source value is at maximum.

Default:

Min/Max:

Units:

20.000 mA, 10.000V

4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V

211

[Analog Out1 Lo]
Sets the Analog Output 1 value when the source value is at minimum.

Default:

Min/Max:

Units:

0.000 mA, 0.000V

4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V

212

[Analog Out2 Sel]
Selects the source for Analog Output 2.

Default:

Options:

0 = AC Line Freq

See

[Analog Out1 Sel]

Table

213

[Analog Out2 Hi]
Sets the Analog Output 2 value when the source value is at maximum.

Default:

Min/Max:

Units:

20.000 mA, 10.000V

4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V

214

[Analog Out2 Lo]
Sets the Analog Output 2 value when the source value is at minimum.

Default:

Min/Max:

Units:

0.000 mA, 0.000V

4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V

Fil

e

Gr

oup

No.

Parameter Name & Description

Values

Bit
Definition

An

al

og

O

ut

2

An

al

og

O

ut

1

Default

x

x

x

x

x

x

x

x

x

x

x

x

x

x

1

1

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

1 = Absolute
0 = Signed
x = Reserved

Options

[Analog Out1 Lo] Value

[Analog Out1 Hi]
Value

Parameter [Anlg Out Absolut] =
Signed

Absolute

0

Input Volt

0V AC

0V AC

200% Rated

(2)

(2)

100% corresponds to parameter 031 [Rated Volts].

1

AC Line Freq

–63.0 Hz

0 Hz

63.0 Hz

2

Total Curr

0 Amps

0 Amps

200% Rated

(3)

(3)

100% corresponds to parameter 032 [Rated Amps].

3

Active Curr

–200% Rated

0 Amps

200% Rated

(3)

4

ReactiveCurr

–200% Rated

0 Amps

200% Rated

(3)

5

Input Curr R

0 Amps

0 Amps

200% Rated

(3)

6

Input Curr S

0 Amps

0 Amps

200% Rated

(3)

7

Input Curr T

0 Amps

0 Amps

200% Rated

(3)

8

DC Bus Volt

0V DC

0V DC

300% Rated

(2)

9

DC Bus Curr

–200% Rated

0 Amps

200% Rated

(3)

10

AC Line kW

–200% Rated

0 kW

200% Rated

(4)

(4)

100% corresponds to parameter 030 [Rated kW].

11

AC Line kVar

–200% Rated

0 kVar

200% Rated

(4)

12

AC Line kVA

0 kVA

0 kVA

200% Rated

(4)

13

Power Factor

-1.00

0

1.00

14

DC Bus V Ref

P080 [V DC]

P080 [V DC]

P081 [V DC]

15

Param Cntl

(1)

(1)

Parameter controlled analog output allows PLC to control analog outputs through datalinks.
Set in parameter 217 [Anlg Out1 Setpt] and parameter 218 [Anlg Out2 Setpt].

16

TestPt Data1

-32767

0

32767