AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring

Consider all of the general specifications dictated by the environment of the
installation, including temperature, flexibility, moisture characteristics, and
chemical resistance. In addition, include a braided shield, specified by the cable
manufacturer as having coverage of at least 75%. An additional foil shield can be
greatly improve noise containment.

A good example of recommended cable is Belden® 29528 - 29532 (AWG-1
through AWG-410). This cable has three XLPE insulated conductors plus
ground with a spiral copper shield surrounded by a PVC jacket.

Armored Cable

Cable with continuous aluminum armor is often recommended in drive system
applications or specific industries. It offers most of the advantages of standard
shielded cable and also combines considerable mechanical strength and resistance
to moisture. It can be installed in concealed and exposed manners, and removes
the requirement for conduit (EMT) in the installation. It can also be directly
buried or embedded in concrete.

Because noise containment can be affected by incidental grounding of the armor
to building steel when the cable is mounted, we recommend the armor cable have
an overall PVC jacket. See Chapter 2, ‘Wire Types’ in Wiring and Grounding
Guidelines for Pulse Width Modulated (PWM) AC Drives, publication
DRIVES-IN001.

Interlocked armor is acceptable for shorter cable runs, but continuous welded
armor is preferred.

Best performance is achieved with three spaced ground conductors, but
acceptable performance below 200 HP is provided by use of a single ground
conductor.

Recommended shielded/armored wire is listed in

Table 1

.

Table 1 - Recommended Shielded/Armored Wire for AFE in IP20 2500 MCC Style Enclosure

Location

Rating/Type

Description

Standard
(Option 1)

1000V, 90 °C (194 °F) XHHW2/
RHW-2 Anixter B29528-B29532,
Belden 29528-29532, or
equivalent

Four tinned copper conductors with XLPE insulation.

Copper braid/aluminum foil combination shield and tinned

copper drain wire.

PVC jacket.

Standard
(Option 2)

Tray rated 1000V, 90 °C (194 °F)
RHH/RHW-2 Anixter OLFLEX-
76xxx03 or equivalent

Three tinned copper conductors with XLPE insulation.

corrugated copper tape with three bare copper grounds in

contact with shield.

PVC jacket.

Class I & II;
Division I & II

Tray rated 1000V, 90 °C (194 °F)
RHH/RHW-2 Anixter 7VFD-xxxx
or equivalent

Three bare copper conductors with XLPE insulation and

impervious corrugated continuously welded aluminum
armor.

Black sunlight resistant PVC jacket overall.

Three copper grounds.