Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

99

Programming and Parameters

Chapter 4

DY

NAMIC C

O

NTROL

Curr

en

t L

oo

p

064

[Active I Ref]
Displays the active current reference.

Default:

Min/Max:
Units:

Read Only

+/- 3200.0 Amp
0.1 Amp

065

[Reactive I Ref]
If selected by [Reactive I Sel], this parameter sets the reference for the reactive current. This can be
used for power factor correction of the power system. Positive value gives inductive current; negative
value gives capacitive current. The maximum reactive current is limited by the following formula:

Default:

Min/Max:
Units:

0.0 Amp

+/- Based on parameter 032 [Rated Amps]
0.1 Amp

066

[Active I Kp]
Sets the active current controller gain.

Default:

Min/Max:
Units:

400

0/4000
None

067

[Active I Ki]
Sets the integral gain of the active current controller.

Default:

Min/Max:
Units:

0.0266 sec

0.0000/6.0000 sec
0.0001 sec

068

[Reactive I Kp]
Sets the synchronization controller gain.

Default:

Min/Max:
Units:

2000

0/32000
None

069

[Reactive I Ki]
Sets the integral of the synchronization controller.

Default:

Min/Max:
Units:

0.040 sec

0.000/20.000 sec
0.001 sec

070

[Reactive I Sel]
Selects the source from which the reactive current is taken.

Default:

Options:

0

0
1
2

React I Ref

React I Ref
Analog In1
Analog In2

Limits

075

[Motor Power Lmt]
Sets the limit for motoring power on the AC line.

Default:

Min/Max:
Units:

300.0%

0.1/300.0%
0.1%

076

[Regen Power Lmt]
Sets the limit for regenerative power allowed to the AC line.

Default:

Min/Max:
Units:

-300.0%

-0.1/-300.0%
0.1%

077

[Current Lmt Val]
Sets the current limit value.

Default:

Min/Max:
Units:

1.5 x [Rated Amps]

0.0/Based on Unit Rating
0.1 Amps

078

[DC Bus Lo Alarm]
Sets the lowest acceptable DC bus voltage for the application. A warning is indicated if the DC bus
voltage falls below the value of this parameter.

Default:

Min/Max:
Units:

Based on Unit Rating

0.0/2000.0V DC
0.1V DC

079

[DC Bus Hi Alarm]
Sets the highest acceptable DC bus voltage for the application. A warning is indicated if the DC bus
voltage exceeds the value of this parameter.

Default:

Min/Max:
Units:

Based on Unit Rating

0.0/2000.0V DC
0.1V DC

080

[DC Ref Lo Lmt]
Displays the limit value of the DC bus reference low limitation, which is calculated based on the
voltage class x 1.35 x 1.05.

Default:

Min/Max:
Units:

Read Only

0.0/1500.0V DC
0.1V DC

081

[DC Ref Hi Lmt]
Displays the limit value of the DC bus reference high limitation, which is calculated based on the
voltage class x 1.35 x 1.3 (for 400/480V units) or voltage class x 1.35 x 1.15 (for 600/690V units).

Default:

Min/Max:
Units:

Read Only

0.0/1500.0V DC
0.1V DC

082

[Ground I Lvl]
Sets the limit value of ground current in % of the unit rating before a ground current alarm or fault is
activated. For AFE parallel operation, the values in all AFEs must be set to 100%.

Default:

Min/Max:
Units:

50.0%

0.0/100.0%
0.1% (Based on unit rating)

Fil

e

Gr

oup

No.

Parameter Name & Description

Values

Maximum Reactive I Ref = P032 [Rated Amps]

2

- P004 [Active Current]

2