ASCII I/O Module Tutorial

Chapter 4

4Ć43

Procedure P1

Connect the 1770ĆCB cable, and set your industrial

terminal to alphanumeric mode (check parameters)

Initialize the module by changing PLCĆ3 operation mode

3[ENTER]2[ENTER]

Procedure P2

Enter your data

Procedure P3

Connect the 1775ĆCAT cable, and set your industrial

terminal to PLCĆ3 mode

Procedure P4

Observe how the data string is stored in data table file O6:0

Results The module removed header and trailing characters, and
transferred 15 data characters, the set string length (Figure 3.8)

Figure 3.8

Removed Header and Trailing Characters

1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1

3 header characters removed

4 trailing characters removed

15 character string

0

11837

RADIX = %A START = WO006:0000

WORD #

00000

0

00H00H

1

00H00H

2

3

3

4 5

4

6 7

5

8 9

6

0 1

7

2 3

00010

4 5

6 7

00H00H 00H00H 00H00H 00H00H 00H00H 00H00H

RADIX = %H START = WO006:0000

WORD #

00000

0

0000

1

0000

2

2033

3

3435

4

3637

5

3839

6

3031

7

3233

00010

3435

3637

0000

0000

0000

0000

0000

0000

Notice the following:

Although you entered 22 characters, the module removed the first three

characters and the four trailing characters.

The module transferred 15 characters, the set string length.

In report generation mode you can mix BCD digits with ASCII characters.
The module sets the ASCII data conversion to two ASCII characters per
word. You select the type of data conversion for BCD digits (either three
BCD or four BCD digits per word) in initialization word two (IW2). If

Selecting Report Generation

Mode, Data Conversion, and

BCD Delimiter