Getting Started with Your ASCII Module

Chapter 2

2Ć22

5.

Connect the IT/DH adapter cable between the ASCII module and
channel B of the industrial terminal.

Channel B

Periodically you will have to switch the cables that connect to channel B
of the industrial terminal.

You will use the industrial terminal cable (cat. no. 1775-CAT) when

using the industrial terminal in PLC-3 mode and entering or displaying
data in the PLC-3 data table.

You will use the IT/DH adapter cable (cat. no. 1770-CB) when using

the industrial terminal in alphanumeric mode as an ASCII device
connected to your ASCII module.

Be sure to observe the labels on the cable connectors and connect each

to its designated port.

Also, if the IT/DH adapter cable is too short or not available, make your
own. It should not exceed 50 feet (Figure 1.7).

Figure 1.7

Minimum Connections in the 1770ĆCB Cable

1

2

3

7

18

25

1

2

3

7

18

25

* Protective Ground

Transmitted Data

Received Data

Ground

ASCII Module

Interface Port

Industrial Terminal

Channel B

11819

Connectors:

25Ćpin DĆShell

Male Connector

Cable Kit

1770ĆXXP (each

end)

Cable:

Belden 8723 or

equivalent

* In cable but not

required for ASCII

module