Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 234

Advertising
background image

ASCII Module

For PLCĆ3 Processor

Appendix B

B-12

4. Compute the approximate read or write block transfer time for

channel 1 and channel 3 (Figure A.15).

Figure B.6

Computing Block Transfer for Each Channel

Step 4

Program Scan

Scanner Scan

Block Transfer Timer per Channel

Compute the read or write block transfer time. Example values have been added.

Time (program) = 2.5ms/K words x 20K words

= 2.5ms x 20

= 50ms

Time (read or write) = 231ms for channel 1 and

77ms for channel 3 (from step 3)

Channel 1 = Program Scan + 2[Scanner Scan]

50ms + 2[231ms]

50ms + 462ms

512ms

Channel 3 = Program Scan + 2[Scanner Scan]

50ms + 2[77ms]

50ms + 154ms

204ms

Reducing Scan Time

Due to the asychronous scan relationship between program and
scanner, and the serial operation of each channel in the scanner, we
suggest that you optimize the overall scan time. Although
recommendations are application dependent, we make the following
recommendations as general guidelines:

Whenever possible, control the manner in which block transfer

instructions are enabled. For example, if only a few block transfer
modules require frequent transfer of data, program them to run
continually. Inhibit block transfer instructions of those modules
that require less frequent transfer until enabled by a timer and/or
some application dependent condition.

Advertising