2ć28 – Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 35

Advertising
background image

Getting Started with Your ASCII Module

Chapter 2

2Ć28

In this demonstration you will enter data and observe how it is stored in
the processor data table. You will use the industrial terminal in
alphanumeric mode as an ASCII data terminal when you enter data. Then
you will change the industrial terminal to PLC-3 mode and observe the
transferred data by displaying the contents of the block transfer read file.
You must alternate cables that connect to channel B of the industrial
terminal, one cable for alphanumeric mode, the other for PLC-3 mode.
You will simulate the action of an input bit through the PLC-3 front panel
to enable a write block transfer.

You will use the following procedures.

In Procedure

You Will

P1

Connect the 1770ĆCB cable, and set your industrial

terminal to alphanumeric mode

P2

Enter your data

P3

Connect the 1775ĆCAT cable, and set your industrial

terminal to PLCĆ3 mode

P4

See how data is stored in the data table

Even if you are familiar with these procedures, read them completely. If
you deviate from these procedures, proper operation may not occur.

If you have not already done so, load the “Getting Started Program”
(Figure 2.8) into processor memory.

Procedure 1
Set Your Industrial Terminal to Alphanumeric Mode

1.

Turn on the industrial terminal.

2.

Connect the 1770-CB cable to channel B of the industrial terminal.

3.

Select alphanumeric mode.

Press [SHIFT][MODE] 2

The CHANNEL ACTIVE LED on the module illuminates.

Reading Data from Your ASCII

Device

Advertising