Ascii module plc-2 family processors appendix a – Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 199

Advertising
background image

ASCII Module

PLC-2 Family Processors

Appendix A

AĆ31

Figure A.11

Example Block Transfer Operation

EN

BTR
BLOCK XFER READ
RACK
GROUP
MODULE

012

7

1=HIGH

FD110:0000

DN

64

FB200:0012

ER

DATA
LENGTH
CNTL

CNTL

CNTL

CNTL

12

15

13

Data File

(Up to 64 words)

FD110

FB200

0

63

12

21

Control File

(10 words)

ASCII

I/O Module

Block Transfer instruction goes true.

Appropriate status bits are set/reset, and the control file tells the

I/O scanner module the address of the data file.

Data from the block transfer I/O module is transferred to the block transfer

data file in the processor data table.

Upon completion of the block transfer, the appropriate status bits are set/

reset.

NOTE: The direction of data flow is reversed for a write block transfer

operation.

Rack 12,

Module Group 7,

Upper Slot

Word

File

You must create the data file

large enough to handle the block

length that you entered in the block

transfer instruction.

This file is created automatically

when you

enter the block transfer instruction

into your program.

Data

Flow

4

2

3

1

1

2

3

4