Choosing Module Features

Chapter 3

3Ć8

Figure 2.4

Current Loop Connections (500 ft. max): Device is Passive Transmit, Passive Receive

(Refer to specifications in Appendix D)

12

24

Transmitted Data

(+)

Drain Wire (Shield)

To I/O

Chassis

Ground

1

ASCII Module

Device

Belden

8723

or

Equiv.

1

Return

Passive

Receive
(-)

13

11

Received Data

(+)

Return

Transmit with

Current Source
(-)

Solder an external ground wire (14 ga.) to the drain wire at the cable connector.

Connect it to the I/O chassis ground lug. Ground the shield at this end only.

11824

Passive Transmit

Passive Receive

Power

Supply

+

-

4-20mA mark state

Figure 2.5

Current Loop Connections (500 ft max.): Device is Active Transmit, Active Receive

(Refer to specifications in Appendix D)

12

24

Transmitted Data

(+)

Drain Wire (Shield)

To I/O

Chassis

Ground

1

ASCII Module

Device

Belden

8723

or

Equiv.

1

Return

Passive

Receive
(-)

11

18

Received Data

(+)

Return

Passive

Transmit
(-)

Solder an external ground wire (14 ga.) to the drain wire at the cable connector.

Connect it to the I/O chassis ground lug. Ground the shield at this end only.

11825

Transmit with

Current Source

Receive with

Current Source

NOTE: Device and its power supply must float in respect to the module for passive transmit.

.