Choosing Module Features

Chapter 3

3Ć4

AĆB Long Line
Use A-B Long Line for communicating up to 5000 cable feet between an
industrial terminal, serving as an ASCII device, and the ASCII module.

Refer to Table 2.D for a detailed listing of A-B Long Line pin functions.

Table 2.D

AĆB Long Line Connector Pin Functions

Pin No.

Signal Name

Source

Function

2

Transmitted Data

AĆB Long Line Device

Data Transfer to 1771ĆDA

7

Transmitted Data Return

Return for transmitted data

11

Received Data

1771ĆDA

Data transfer to AĆB Long Line Device

25

Received Data Return

Return for received data

Selecting the Communication Mode

The communication mode that you choose depends on the cable distance
from your ASCII device to your ASCII module, and on characteristics of
your ASCII device (Table 2.E).

Table 2.E

Mode of Communication

If Distance is

Less Than

And Your ASCII Device is a

Then Choose this

Transmission Mode

50 feet

Data Terminal Equipment (DTE) and conforms

to RSĆ232ĆC

without control lines

with control lines

Data Set (modem) and conforms to RSĆ232ĆC

without control lines

with control lines

RSĆ232ĆC (Figure 2.1)

4Ćwire cable

8Ćwire cable

RSĆ232ĆC (Figure 2.2)

4Ćwire cable

8Ćwire cable

500 feet

DTE and provides a 20mA current source for

the transmit line, only

DTE and requires a 20mA external current

source for its transmit line

DTE and provides 20mA current sources for

transmit and receive lines

Current Loop (Figure 2.3)

The module powers its own transmit line.

Current Loop (Figure 2.4)

You add the power supply for the DTE.

Current Loop (Figure 2.5)

The module operates in passive transmit.

5000 feet

AĆB industrial terminal or contains a line driver

receiver for AĆB long line operation.

AĆB Long Line (Figure 2.6)

Advertising