Choosing Module Features

Chapter 3

3Ć9

Use a 25-pin male D-shell connector such as Amp DB-25P for your cable
connections to the ASCII module. Terminate the shield to pin 1 at the
module end only.

Figure 2.6

AĆB Long Line Connections (5000 ft max)

2

25

3

2

7

11

Receive

Receive

Transmit

Drain Wire (Shield)

To I/O

Chassis

Ground

1

ASCII Module

Industrial Terminal

Channel B

18

25

Transmitted Data

Return

Received Data

Return

1 Solder an external ground wire (14 ga.) to the drain wire at the cable connector.

Connect it to the I/O chassis ground lug. Ground the shield at this end only.

11826

Belden

8723 or

Equiv.

Figure 2.7

RSĆ232ĆC Simplex Write Connections

(Refer to Specifications in Appendix D)

7

7

Receive

Transmit

Drain Wire (Shield)

To I/O

Chassis

Ground

[1]

ASCII Module

Device

(DTE)

3

3

Signal Ground (AB)

Received Data (BB)

11827

NOTE: Jumper pin 2 to pin 18 at the module end of the cable (special case).

Solder an external ground wire (14 ga.) to the drain wire at the cable connector.

Connect it to the I/O chassis ground lug. Ground the shield at this end only.

(DCE)

2

18

Belden

8723

or

Equiv.

[1]