ASCII Module

PLC-2 Family Processors

Appendix A

AĆ12

Figure A.5

Local System Example

1771-AL

1771-DA

Rack No. 1

1771-AL

1771-DA

Rack No. 2

1771-AL

1771-DA

Rack No. 3

1771-AL

1771-DA

Rack No. 4

11841

PLC-2/30

Solution:

The facts of the problem are:

Program length = 4K words
Number of chassis = 4 rack numbers
Number of block transfer words, W = 64 (read) or 2 (write)

1.

Calculate the system values.

Processor Scan Time, PS = (5ms/1K words) x (4K words) = 20ms
Processor I/O Scan Time, PIO = (0.5ms/rack number) x(4 rack
numbers) = 2ms
Number of Words Transferred, W = 64(read) or 2 (write)