ASCII I/O Module Tutorial

Chapter 4

4Ć11

Notice the following:

The new string (data and fill characters) completely replaced the

previous data.

The data is right justified.
Fill character spaces (20) were added by the ASCII module.

String Length Greater Than Module's String Length

When the module receives a string of data greater than the set string
length, it does the following:

Immediately transfers the number of characters equal to its set string

length to the processor.

Sets bit 14 in status word one, Input String>Maximum, SW1(14). Bit

14 is immediately reset when the processor confirms receipt of data.

Retains the balance of data in its input buffer.
Transfers the balance of data with new data when it receives enough

new data to complete the string, or when the new data contains an
end-of-string delimiter.

In this demonstration you will enter a string of data greater than the set
string length and observe its storage in the data table. (The set string
length, IW2(00-13), is 15 characters.)

1. Enter 12345678901234567890

Do not enter [RETURN]

Refer to procedures in section titled “Reading Data from Your ASCII
Device”, P. 1-10.

Procedure P1 Set your industrial terminal to alphanumeric mode

Procedure P2 Enter your data

Procedure P3 Set your industrial terminal to PLCĆ2 mode

Procedure P4 Observe how data is stored in the data table

Results The read block transfer file displays the number of characters
equal to the string length, 15, in positions 003 thru 010 (Table 3.F).