Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 158

Advertising
background image

Function of Control/Status Bits

Chapter 6

6Ć23

Status Word One

Bit

Function

Status*

17

Channel Active

0 = Reset

1 = The ASCII device is enabled

16

Write Data

Acknowledge

Module toggles SW1(16)=CW1(16) to tell

PC that new data was received

15

Read Data Available

Module toggles SW1(15)

CW1(15) when

it detects a change in status or receives

new data from ASCII device

14

Input String Exceeds

Maximum

0 = Reset

1 = Input string >set string length in

IW2(00Ć13)

13

ASCII Device/Link

Error

0 = Reset

1 = Module detects parity, framing or

overrun error in string from the ASCII

device

12

Initialization Error

0 = Reset

1 = Module ceases to operate

11

Not Used

Module sets it to zero

10

Data Complete

0 = Reset

1 = Module detects delimiter at end of

string that is distributed over one or

more block transfers.

07

PowerĆup

Initialization

0 = Reset by CW1(07)

1 = PowerĆup initialization is complete

06

Not used

Module sets it to zero

05

Output Buffer Full

0 = Reset when less than full

1 = Output buffer full

04

Output Buffer Empty

0 = Reset when data enters buffer

1 = Output buffer empty

03

Input Buffer full

0 = Reset by CW1(03) when input buffer is

empty

1 = Input buffer is full

02

Input Buffer 75% Full

0 = Reset when less than 75% full

1 = Input buffer is 75% full

01

Input Buffer 50% Full

0 = Reset when less than 50% full

1 = Input buffer is 50% full

00

Input Buffer Empty

0 = Reset when data enters buffer

1 = Input buffer is empty

*The module sets these bits (unless toggled) when it detects the subject condition.