Function of Control/Status Bits

Chapter 6

6Ć20

Initialization Word One

Bit

Function

Status

17

ACK/NAK

0* = Not used by ASCII device

1 = ACK/NAK required by device

16

Stop Bits

0* = Device generates one stop bit

1 = Device generates two stop bits

15

Parity Enable

0* = Device does not use parity bit

1 = Device generates a parity bit

14

Parity

0* = Odd

1 = Even

13

Number of Data Bits

0* = Device generates 8Ćbit data

1 = Device generates 7Ćbit data

12, 11, 10 Communication

Rate

000* = 300 baud

001 = 600 baud

010 = 1200 baud

011 = 2400 baud

100 = 4800 baud

101 = 9600 baud

110 = 110 baud

111 = 110 baud

07, 06, 05 Mode of

Transmission

000* = Full duplex with echo

001 = Full duplex without echo

010 = Simplex read

011 = Simplex write

100 = Half duplex with echo

101 = Half duplex without echo

all other codes are invalid

04, 03, 02 Mode of Operation

000* = Data mode

001 = Report Generation (RG) mode

01, 00

Number of

Initialization Words

00* = Word 1

01 = Words 1 and 2

10 = Words 1, 2, and 3

11 = Words 1, 2, 3, and 4

*Default value when you do not select that initialization word