Selecting delay for carriage returns, Setting remaining bits in iw, 3ć26 – Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual
Page 68
Choosing Module Features
Chapter 3
3Ć26
Record your choice by writing a 0 (single transfer) or 1 (multiple transfer)
in IW2(17). Use the form (found at the end of this chapter) or the boxes
below.
IW2
Single
or Multiple
17
Transfers
When using an unbuffered data terminal, select a time for the ASCII
module to delay outputting data while the mechanical carriage return is
operating. Your selections are:
Delay Time (ms)
Code
0
00
50
01
100
10
200
11
Record your selection by writing the code in IW3(07,06) using the form
(found at the end of this chapter) or the boxes below.
IW3
Delay for
Carriage Return
07 06
Set the remaining bits in initialization word one according to the
specifications of your ASCII device.
Selecting Delay for Carriage
Return, IW3(06Ć07)
Setting Remaining Bits in
IW1(10Ć17)