Choosing the mode of module operation, 3ć13 – Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 55

Advertising
background image

Choosing Module Features

Chapter 3

3Ć13

The mode of module operation that you choose depends on the
application and type of ASCII device. Typically, use data mode when you
are reading data from an ASCII device, such as a bar code reader. Use
report generation mode when you are writing messages to an ASCII data
terminal (Table 2.F).

Table 2.F

Mode of Module Operation

Use

When

Data Mode

All of your data is converted by the ASCII module and stored in the data

table as a single data type using any one of the following data converĆ

sions:

2 ASCII characters per word

1 ASCII character per word

3 BCD characters per word

4 BCD characters per word

4 Hex characters per word

String length is from 1 to 62 characters

You want to select right to left justified margins and/or data

Report Generation Mode

You want to mix ASCII characters with BCD values. In addition to the

2 ASCII characters per word that your module uses in report generation

mode, you must choose one of the following types of data conversion:

3 BCD characters per word

4 BCD characters per word

String length is from 1 to 999 characters

Your margin is left justified for ASCII data but right justified for BCD valĆ

ues within the ASCII data

Select data mode using code 000, or report generation mode using code
001. Record your selection in IW1(02-04) using the initialization word
form (found at the end of this chapter) or the boxes below.

IW1

Mode of

Operation

04 03 02

Choosing the Mode of Module

Operation, IW1(02Ć04)

Advertising