Choosing module features chapter 3 – Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 74

Advertising
background image

Record

Your

Selections

Hex Equivalent

IW1

Record

Your

Selections

Hex Equivalent

IW2

Record

Your

Selections

Hex Equivalent

IW3

Record

Your

Selections

Hex Equivalent

IW4

Form 5176

Initialization Words for Report Generation Mode

* = default value

11833

Choosing Module Features

Chapter 3

3Ć32

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

ACK

NAK

Stop

Bits

Parity

Enable

Parity

Odd,

even

No. of

bits

Communication

Rate

Mode of

Transmission

Mode of

Operation

Number of

Initialization

Words

0 = *

No

1 =

Yes

0 = 1*

Stop

Bit

1 = 2

Stop

Bits

0 = *

No

1 =

Yes

0 = *

Odd

1 =

Even

0 = 8*

Bit

Data

1 = 7

Bit

Data

000 = 300 Baud*

001 = 600 Baud

010 = 1200 Baud

011 = 2400 Baud

100 = 4800 Baud

101 = 9600 Baud

110 = 110 Baud

111 = 110 Baud

000 = Full Duplex w/Echo*

001 = Full Duplex w/o

Echo

010 = Simplex Read

011 = Simplex Write

100 = Half Duplex w/Echo

101 = Half Duplex w/o

Echo

00 = Word 1*

01 = Words

1 & 2

10 = Words

1, 2 & 3

11 = Words

1, 2, 3 & 4

0

0

0

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Rate

Data Conversion

Number of ASCII Characters Per String

0 = *

Single

1 =

Multi.

0 0 1 = 3 BCD

0 1 0 = 4 BCD

Default = 124, Maximum = 999

BCD Digit 2 BCD Digit 1 BCD Digit 0

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Enable

EĆOĆS

Del.

EndĆofĆString Delimiter

(EĆOĆS Del.)

Delay for CR

LF if

CR

Send

EĆOĆS

Del

Data

Just.

I/O Buffer Split

Input/Output

%

0 = *

Yes

1 = No

Null * (CTRL 0)

00 = 0 ms*

01 = 50 ms

10 = 100 ms

11 = 200 ms

0 = *

No

1 =

Yes

0 = *

No

1 =

Yes

0 = *

Right

1 =

Left

000 = 50 / 50 *

001 = 100 / 0

010 = 25 / 75

011 = 25 / 75

100 = 0 / 100

0

0

0

0

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Fill Character Removed

Number of Trailing Characters

Removed

Number of Header Characters

Removed

( : ) *

Must not be same as IW3 (10 Ć 16)

0 * Ć 15

binary

0 * Ć 15

binary

0

0

0

0

Advertising