Choosing Module Features

Chapter 3

3Ć20

The highest number of words that you can transfer in one block transfer is
64. You must include two command words in each write block transfer
and two status words in each read block transfer in addition to your data
words. You can also transfer up to four initialization words (Figure 3.9).

Figure 2.9

Block Lengths for Read and Write Block Transfers

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Command Word No. 1
Command Word No. 2

Initialize Data Word No. 1
Initialize Data Word No. 2
Initialize Data Word No. 3
Initialize Data Word No. 4

Initialization WRITE Block

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Command Word No. 1
Command Word No. 2

WRITE Block

64 Words, max. Data

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Status Word No. 1
Status Word No. 2

READ Block

64 Words, max. Data

The longest data string read from the ASCII device determines the block
length of the read block transfer instruction. In the PLC-2 family, the read
and write block lengths must be equal to ensure correct operation. For
PLC-3 processors, the block lengths can be different.

Determining Block Transfer

Length