Function of Control/Status Bits

Chapter 6

6Ć4

Bits: IW1(02-04)
Function: Mode of Module Operation
Description: Choose data mode (default) when

You want to automatically convert ASCII characters to any one of five

data types for convenient data table storage and usage

Your data string is from 1 to 62 characters

Choose report generation mode when

Your data is message oriented
You want to include BCD numbers in your message
Your data string is from 1 to 999 characters

Select the mode of module operation from the following:

04

03

02

Mode of Operation

0

0

0

0

0

1

Data mode

Report generation

mode

all

other

Invalid

When the module detects an invalid setting of bits 02-04 or bits 05-07, it
faults due to an initialization error. The module disables its interface port
and sets status bit SW1(12).

Bit: IW1(05-07)
Function: Mode of Transmission
Description: The modes of transmission that the module can handle are
full or half duplex with or without echo, and simplex read or write. The
codes for setting modes of transmission are:

07

06

05

Mode of Transmission

0

0

0

0

1

1

0

0

1

1

0

0

0

1

0

1

0

1

Full duplex with echo

(default)

Full duplex without echo

Simplex read

Simplex write

Half duplex with echo

Half duplex without

echo

all

other

Invalid