Selecting the number of initialization, 3ć29 – Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 71

Advertising
background image

Choosing Module Features

Chapter 3

3Ć29

Record features that apply to your ASCII device by writing a 0 or 1 in
corresponding bits IW1(10-17) using the form (found at the end of this
chapter) or the boxes below.

IW1

Bit Number

17 16 15 14 13 12 11 10

Communciation rate code

Number of Data Bits: 0=8, 1=7

Parity: 0=Odd, 1=Even

Parity Enable: 0=No, 1=Yes

Stop Bits: 0=one, 1=two

ACK/NAK: 0=No, 1=Yes

Select the number of initialization words for transfer to the ASCII module
after deciding which of the module features are required for your ASCII
device and application. You select module features by setting bits in four
initialization words. Set the number of initialization words equal to the
highest numbered initialization word used. For example, if you need a
feature found in word four, you must select all four initialization words.

Number of Words

Code

Word 1

00

Words l and 2

01

Words 1, 2, and 3

10

Words 1, 2, 3, and 4

11

Review your selections of module features. Record the code for the
number of initialization words that you need in IW1(00-01). Use the form
(found at the end of this chapter) or the boxes below.

IW1

Initialization

Words

01

00

Number of

Selecting the Number of

Initialization Words, IW1(00Ć01)