7 - troubleshooting, Chapter objectives, Recognizing initialization errors – Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 160: Troubleshooting

Advertising
background image

Chapter

7

7Ć1

Troubleshooting

In this chapter you will read about recognizing initialization errors,
interpreting status indicators, and status codes for troubleshooting
purposes. We will also show you how to conduct a test to verify that your
ASCII module is operating correctly.

If you should set bits of initialization words to an invalid range, the
module detects an initialization error and will not operate. Invalid settings
of initialization words are listed in Table 6.A.

Table 6.A

Initialization Errors

Feature

Word (Bit)

Invalid Setting or Range

Mode of module operation

IW1(02Ć04)

Above 001 (binary)

Mode of transmission

IW1(05Ć07)

Above 101 (binary)

String length

IW2(00Ć13)

Data mode:

above 62 characters

Either mode:

nonĆBCD digits using

AĆF hex

Data conversion

IW2(14Ć16)

Data mode:

above 100 (binary)

Report generation mode:

000=1 ASCII/word

011= 2 ASCII/word

100= 4 hex/word

above 100 (binary)

I/O buffer split

IW3(00Ć02)

Simplex read:

100=100% output

Simplex write:

001=100% input

Send EOS delimiter to PC

IW3(04)

Set in data mode

Chapter Objectives

Recognizing Initialization Errors