Block transfer – Rockwell Automation 2706 DL40 HARDWARE USER MANUAL User Manual

Page 110

Advertising
background image

Chapter 10
Using Remote I/O

10 – 18

WORD 1

17 16 15

14

WORD 0

Handshake Bit

Input Image Table - 3/4 rack

Clock/Date Data Bit = 1

Diagnostic Code

Hour/Month

Minute/Day

Second/Year

WORD 2

Always Returned Empty

WORD 3

Always Returned Empty

WORD 4

Always Returned Empty

WORD 5

Always Returned Empty

WORD 6

Always Returned Empty

WORD 7

Always Returned Empty

WORD 1

17 16 15

14

WORD 0

Handshake Bit

Input Image Table - Full rack

Clock/Date Data Bit = 1

Diagnostic Code

Hour/Month

Minute/Day

Second/Year

WORD 2

Always Returned Empty

WORD 3

Always Returned Empty

WORD 4

Always Returned Empty

WORD 5

Always Returned Empty

WORD 6

Always Returned Empty

WORD 7

Always Returned Empty

Block Transfer

NOTE: If Block Transfer DIP Switch (Switch 2–4) is enabled, all functions
between the PLC and DL40 must be made by Block Transfer.

Important: The block transfer must be configured as non–continuous using

ladder logic consistent with the following: