Ac sampling – Rockwell Automation 2706 DL40 HARDWARE USER MANUAL User Manual

Page 92

Advertising
background image

Chapter 9
Using the Parallel Port

9 – 8

Important: To input AC into the Parallel Port, two AC to DC Converters
(Catalog Number 2706–NG2) must be used. When using a converter,

Using

AC/DC Converter

in the Triggering Port Setup must be set to

Yes

. This will

prevent

Data Hold Time

from being set to less than 40 msec. Conversion

time must be added to the

Data Hold Time

.

34 msec

NG2 conversion time

+

Data Hold Time (40 msec minimum)

Total hold time for your data

AC Sampling