Message/variable/slave run mode – Rockwell Automation 2706 DL40 HARDWARE USER MANUAL User Manual

Page 37

Advertising
background image

Chapter 4
The Run Mode – Parallel Port

4 – 2

Table 4.A
Summary of Parallel Port Run Mode Types

Feature

Message/Variable/Slave Run

Mode

Message List Run Mode

Trigger messages

Trigger a message with 1 to 40
variables, depending on trigger
method and and variable type

Triggers a message list of up to 20
messages in Round Robin Order

Send messages to slave display

Slave address for each message
can be specified with message
trigger. (Overrides address
specified as Message Attribute)

Slave address specified as a
Message Attribute

Send variables to place in
message

D Up to 10 (16 bit) binary or (4

digit) BCD

D Up to 20 (8 bit) ASCII

D Up to 40 (4 bit) BCD

No

Variable types

Binary – Signed and Unsigned BCD
ASCII

Not Applicable

Message acknowledgement

Yes

Input and display of ASCII input
data (via keyboard port)

Up to 20 ASCII characters

Return ASCII input data via
RS-485 port

Up to 20 characters

Put message on Historical Events
Stack

Yes

In the Message/Variable/Slave Run Mode you can:

Trigger Messages Via the Parallel Port

You can trigger a single message. See Chapter 9 for more information.

Trigger Messages Via the Keyboard Port or the RS-485 Port

See Chapter 9 for more information.

Send Variables to be Included In Message

Your PLC can include variables with the message trigger. Up to the
equivalent of 10 full word variables can be sent with the message trigger.

Variable types include:

16 bit binary (1 variable per word)

8 bit ASCII (2 per word)

4 digit signed Binary Coded Decimal (BCD) (1 per word)

1 digit (4 bit) unsigned BCD (4 per word)

Message/Variable/Slave
Run Mode

Advertising