Chapter 6
Other Operating Modes

6 – 13

Parameter

Available choices

Baud Rate

300, 1200, 2400, 4800, 9600, 19200

Data Bits

7 or 8

Parity

None, Odd, Even

Port Use

DL40 Programmer, DL Slaves, Devices Using
Open Protocol

➀ This setting should always be 8 if Port Use is set to Programmer.

➁ This setting should always be None if Port Use is set to Programmer.

Important: Do not set Port Usage to DL Slaves or Devices Using Open

Protocol if downloading message files to the DL40 via the
RS-485 Port.

Triggering Port Settings

The parameters presented here will differ between Remote I/O and Parallel
Port versions of the DL40 Message Display. The following settings are
available only on Remote I/O units. The default value appears in bold.

Parameter

Available choices

Message Format

Binary, BCD

Variable Format

Binary, BCD

Control-W Format

BCD, ASCII

Bit Trigger Priority Section
Size

0 to 31 words

Always Send Clock Data

Yes or No

➀ If selection is Yes, only clock data will be returned to a PLC no matter what attributes

are set or what data is requested.

The following settings are available only on Parallel Port units. The default
value appears in bold.