Chapter 12
DIP Switch Settings

12 – 2

Setting Switch Bank #1

Presented in Table 12.A through Table 12.C are functions and settings for
Switch Bank #1 for the PLC-2 family. Rack address settings for PLC-3 and
PLC-5 are listed in Table 12.D.

Note: the rack address settings apply only to PLC-2 or 1771-SN
Sub-Scanner.

Note: A DIP switch is ON when in the “up” position.

Table 12.A
Switch Bank #1 when using DL40s with:
– PLC-2 with Remote I/O
– Any 1771
SN Sub-Scanner Application
(Remote I/O Units)
–SLC with 1747-SN Block Transfer

Specifying Rack Address of PLC-2

I/O Rack

Switch Settings

Address

1

2

3

4

5

6

1

ON

ON

ON

ON

ON

ON

2

ON

ON

ON

ON

ON

OFF

3

ON

ON

ON

ON

OFF

ON

4

ON

ON

ON

ON

OFF

OFF

5

ON

ON

ON

OFF

ON

ON

6

ON

ON

ON

OFF

ON

OFF

7

ON

ON

ON

OFF

OFF

ON

Table 12.B
Specifying First I/O Group

First I/O

Switch Settings

Group

7

8

0

ON

ON

2

ON

OFF

4

OFF

ON

6

OFF

OFF

Table 12.C
Specifying I/O Rack Size

Rack

Switch Settings

Size

9

10

1/4

ON

ON

1/2

ON

OFF

3/4

OFF

ON

Full

OFF

OFF